Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1408-EM3A-ENT |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Type | 3-Phase Power Monitoring and Protection Module |
| Input Voltage | Up to 690V AC L-L (phase-to-phase), direct connection or via PTs |
| Input Current | Up to 5A AC, direct connection or via CTs (Current Transformers) |
| Power Supply | 24-240V AC/DC (wide range) or 125V DC |
| Measurement Parameters | Volts (L-L, L-N), Amps, kW/kVAR/kVA, kWh/kVARh, Power Factor, Frequency, Harmonics (THD) up to the 63rd |
| Accuracy | Class 0.5% for Active Energy (kWh) per IEC 62053-22 |
| Communication Ports | 1 x 10/100 Mbps Ethernet port (EtherNet/IP), 1 x RS-485 serial port (Modbus RTU) |
| Protocols | EtherNet/IP, Modbus RTU/TCP, DNP3, Web Server (HTTP) |
| Display | Optional local display module (1408-DD1) available |
| I/O Capabilities | Configurable digital inputs and outputs (via add-on modules or internal logic) |
| Operating Temperature | -20°C to 70°C (-4°F to 158°F) |
| Enclosure Rating | Panel mount, IP20 (requires enclosure for protection) |
Main Features and Advantages
Comprehensive Power Quality and Energy Analytics: The Allen-Bradley 1408-EM3A-ENT goes beyond basic metering. It provides detailed power quality analysis, capturing critical data such as voltage and current total harmonic distortion (THD), individual harmonic magnitudes, voltage sags/swells, and transients. This allows engineers to diagnose power system issues, such as transformer overheating or nuisance breaker trips caused by harmonics from non-linear loads like variable frequency drives. For energy management, it measures all key parameters including import/export energy, demand (kW), and peak demand, enabling accurate utility bill verification, load profiling, and identification of energy-saving opportunities. The high accuracy of the 1408-EM3A-ENT Powermonitor 1000 ensures reliable data for sub-metering and cost allocation across different departments or processes.Seamless Network Integration and Advanced Connectivity: The integrated EtherNet/IP port is a defining feature, allowing the Allen-Bradley 1408-EM3A-ENT to function as a native node on a plant-wide control and information network. This enables real-time, high-speed data exchange with Logix controllers and FactoryTalk software suites, facilitating automated control strategies—like demand response or load shedding—based on real-time power data. The built-in web server provides secure, direct access to a rich graphical interface via a standard web browser, allowing for configuration, data viewing, and report generation from any connected workstation without specialized software. Additionally, the RS-485 serial port supports legacy protocols like Modbus RTU, offering connectivity flexibility. The device’s programmable logic and configurable I/O (with add-ons) allow it to perform local control functions, such as alarming or load switching, without relying on a central PLC, making it an intelligent edge device.
Application Field
The Allen-Bradley 1408-EM3A-ENT Powermonitor 1000 is deployed across a wide spectrum of applications where electrical system visibility and control are paramount. In Industrial Manufacturing Plants, it is used for main incoming service monitoring, substation monitoring, and critical feeder and load monitoring. It helps manage peak demand charges, monitors the health of large motors and drives, and identifies harmonic pollution sources. In Commercial Buildings and Data Centers, the 1408-EM3A-ENT is essential for energy management and submetering of tenants, floors, or specific high-consumption loads like HVAC systems and server rooms, supporting LEED certification and sustainability reporting.Within Water and Wastewater Treatment Facilities, the module monitors large pumps, blowers, and treatment processes, optimizing energy usage—often the largest operational cost. Its power quality monitoring helps protect sensitive control equipment. In the Renewable Energy and Microgrid sector, it is used at the point of interconnection for solar PV farms or combined heat and power (CHP) systems to monitor generation, import/export, and power quality for utility compliance. The Allen-Bradley 1408-EM3A-ENT is also ideal for Infrastructure and Transportation projects, such as monitoring traction power substations for rail or electrical distribution in airports, ensuring system reliability and efficient energy use. Its ability to provide detailed, timestamped data makes it invaluable for forensic analysis following equipment failure or power quality events.