Technical Specifications
| Parameter Name | Value |
|---|---|
| Product Model | Allen‑Bradley 1769‑IF16V |
| Manufacturer | Rockwell Automation / Allen‑Bradley |
| Product Type | Analog Voltage Input Module |
| Series | 1769 Compact I/O / CompactLogix |
| Number of Inputs | 16 (single‑ended/differential, software configurable) |
| Input Ranges | ±10V DC, 0‑10V DC, 0‑5V DC, 1‑5V DC |
| Resolution | 16 bits (unipolar) / 15 bits + sign (bipolar) |
| Input Impedance | ≥ 1 MΩ |
| Accuracy (25°C) | ±0.05% of full scale |
| Common Mode Rejection Ratio (CMRR) | > 90‑100 dB @ 50/60 Hz |
| Input Linearity | ±0.03% |
| Channel Scan Time | 8.7 ms (all channels) |
| Channel‑to‑Channel Isolation | 500V AC / 710V DC for 1 minute |
| Working Voltage Isolation | 30V AC/DC continuous |
| Backplane Current Draw (5V DC) | 60‑190 mA |
| Backplane Current Draw (24V DC) | 25‑70 mA |
| Power Dissipation | 7.5 W typical |
| Operating Temperature | 0°C to 60°C |
| Storage Temperature | ‑40°C to 85°C |
| Dimensions (W x H x D) | 35 x 87 x 118 mm |
| Weight | Approximately 0.24‑0.25 kg |
| Mounting | DIN Rail or Panel Mount |
| Power Supply Distance Rating | 8 modules maximum |
| Status Indicators | Module status LED, 24V sensor power status LED |
| Wiring | 2x 8‑channel removable terminal blocks |
Main Features and Advantages
High‑Density 16‑Channel Architecture with Space‑Saving Design
The Allen‑Bradley 1769‑IF16V delivers an industry‑leading 16 analog input channels within a single 1769 module slot, effectively doubling the channel density compared to standard 8‑channel analog modules while maintaining the compact footprint of the Compact I/O platform. This high‑density architecture reduces the number of modules required for large‑scale analog monitoring applications, saving valuable control panel space and minimizing backplane slots for system expansion. The 1769‑IF16V employs differential input technology on all 16 channels, providing superior common‑mode noise rejection for accurate signal acquisition even when sensors are located at considerable distances from the controller. With a high input impedance of ≥1 MΩ, the module minimizes loading effects on connected sensors, ensuring that measurement accuracy is preserved and sensor performance is not degraded by the measurement circuit.
Superior Signal Integrity with Channel‑to‑Channel Isolation
A defining feature of the 1769‑IF16V is its comprehensive channel‑to‑channel isolation, rated at 500V AC for 1 minute, which provides robust protection against ground potential differences, electrical noise, and transient overvoltages that commonly affect multichannel analog systems. This isolation ensures that a fault condition on one input channel does not propagate to adjacent channels, safeguarding measurement integrity and protecting the controller from damaging voltage excursions. The 1769‑IF16V achieves an impressive common‑mode rejection ratio exceeding 90 dB at 50/60 Hz, effectively attenuating interference from power lines and variable frequency drives. The 16‑bit resolution translates to measurement granularity of approximately 0.3 mV for a ±10V input range, providing the precision necessary for demanding process monitoring and quality control applications.
Software‑Configurable Versatility and Seamless Integration
The 1769‑IF16V eliminates the need for hardware jumpers or DIP switches, allowing all channel‑specific configuration—including input range selection, data format, and filter settings—to be performed directly through Studio 5000 or Connected Components Workbench software. Each of the 16 channels can be independently configured for different input ranges, enabling a single 1769‑IF16V to accommodate diverse sensor types simultaneously, a capability that significantly simplifies system design and reduces spare parts inventory. The module supports both engineering unit scaling (raw counts to real‑world values) and direct reading of percentage or scaled values, streamlining programming efforts and facilitating intuitive interpretation of process data within the control application. With a scan time of 8.7 ms for all 16 channels, the 1769‑IF16V offers a balance of speed and precision that suits the majority of industrial process monitoring applications, providing timely data updates for responsive control decisions.
Application Fields
Industrial Process Monitoring and Control
The Allen‑Bradley 1769‑IF16V is extensively deployed in process industries where continuous monitoring of multiple process variables is essential for efficient operation and quality assurance. In a typical chemical processing facility, multiple 1769‑IF16V modules interface with pressure transmitters, temperature transmitters, and level sensors, providing the CompactLogix controller with real‑time process data for PID loop control, batch sequencing, and alarm management. The 16‑channel density of the 1769‑IF16V enables consolidation of analog input signals that would otherwise require multiple modules, simplifying system architecture and reducing installed cost. The module’s high‑resolution A/D conversion and excellent noise rejection make it particularly suitable for applications where precision measurement is critical, such as pH control and flow ratio monitoring.
Test and Measurement Systems
In automated test equipment and data acquisition applications, the 1769‑IF16V provides the high channel count and precision required for multi‑parameter testing of electromechanical assemblies. The module’s differential inputs and channel‑to‑channel isolation are particularly advantageous in test applications where sensors may operate at different ground potentials, preventing measurement errors that could compromise product qualification decisions. For example, in motor test stands, a single 1769‑IF16V can monitor winding temperatures from multiple thermocouple transmitters, bearing vibration sensor outputs, and torque transducer signals simultaneously, delivering comprehensive test data to the control system for pass/fail determination and trend analysis.








Reviews