📦Product Overview
The CS513(3BSE000435R1)is a high-performance,redundant CPU module designed for mission-critical process control applications.It serves as the central brain of an ABB DCS rack,running real-time control strategies(e.g.,PID loops,interlocks,sequencing)with high reliability and fault tolerance.
It is typically used in:
Thermal power plants(boiler control,turbine protection)
Combined cycle and CHP plants
Refineries and chemical processing
Water treatment and district heating systems
🧩Technical Specifications
Parameter Specification
Part Number 3BSE000435R1
Model CS513
Manufacturer ABB
System ABB Advant OCS,Symphony Harmony,Symphony Plus
Function Redundant CPU/Controller Module
Processor Intel i386 or compatible(industrial-grade,~20–33 MHz)
Memory 4 MB RAM(typical),expandable via memory cards
Redundancy Yes–supports 1:1 hot-standby redundant pair
Firmware Storage EPROM or flash memory for program retention
Backplane Bus S900 or S800 I/O Bus(depending on chassis)
Communication Ports:
-Optical Fiber(FO)For redundant link to standby CPU
-RS-485/MB+For connection to MMI,historians,or gateways
-Ethernet(optional via adapter)For engineering access
Hot-Swappable Yes–supports online replacement
Diagnostics LED indicators for RUN,FAIL,RDY,COMM,BAT
Power Supply+5 VDC from backplane(via S100/S900 rack)
Operating Temp 0°C to 60°C(32°F to 140°F)
Storage Temp-40°C to 85°C
Humidity 5%to 95%RH,non-condensing
✅Key Features
High Availability:Dual CS513 modules operate in active/standby(hot backup)mode.If the primary fails,the standby takes over within milliseconds—bumpless transfer.
Deterministic Control:Executes control logic in fixed scan cycles(e.g.,100 ms to 1 s),critical for stable process regulation.
Integrated Redundancy Link:Uses fiber optic cable between two CS513 units to synchronize program state,memory,and I/O images.
Programmable in ABB Languages:
Function Block Diagram(FBD)
Sequential Function Chart(SFC)
Ladder Logic(LD)via Add-On Instructions
Using ABB Control Builder F or Control Builder Plus software.
Large I/O Capacity:Can manage hundreds of I/O points via S900 or S800 remote I/O modules.
Event Logging&Time Stamping:Supports precise event sequence recording(important for fault analysis).
🔗Typical System Architecture
[Operator Station(Advant HM)]
↓(Ethernet/MB+)
[CS513 Primary CPU]←→[CS513 Standby CPU]←Fiber Redundancy Link
↓(Backplane)
[S900/S800 I/O Modules]→Field Sensors&Actuators
↓
[Gateways to PLCs,Drives,SCADA]
🏭Common Applications
Boiler Control Systems:Combustion management,drum level control.
Turbine Governor&Protection:Overspeed,vibration monitoring.
Burner Management Systems(BMS):Safety interlocks and flame supervision.
Balance of Plant(BOP):Cooling water,fuel gas,air compressor control.
Legacy DCS Upgrades:Often found in systems being migrated to 800xA.
🔧Installation&Maintenance Tips
Redundancy Setup:
Install two CS513 modules in redundant slots(e.g.,Slot 1&2).
Connect them via fiber optic cable(FOI-2 or equivalent).
Configure one as ACTIVE,the other as STANDBY using Control Builder.
Firmware&Memory:
Use memory expansion cards(e.g.,3BHE003617R0101)for larger programs.
Ensure firmware version matches across system components.
LED Indicators:
Green RUN:Module operating normally
Red FAIL:Hardware or software fault
Yellow RDY:Ready(standby mode)
Blinking COMM:Data exchange with peer CPU
Hot Swap:
Safe to replace under power,but ensure standby unit is healthy first.
Battery Backup(if applicable):
Some versions use a CMOS battery to retain clock/time–check every 3–5 years.
🔄Related Products
Part Number Description
3BSE000436R1 CS514–Similar CPU,often with enhanced memory or comms
3BSE000437R1 CS515–Later generation processor
3BSE000438R1 CS516–Ethernet-enabled CPU
3BSE000166R1 FOI-2 Fiber Optic Interface(for redundancy link)
3BSE000167R1 MB+Communication Module
S900 I/O Chassis Rack for mounting CS513 and I/O modules
Control Builder F/Plus Engineering software for programming
❗Obsolescence&Modernization
The CS513(3BSE000435R1)is a legacy DCS processor.ABB has largely transitioned to the 800xA platform with AC 800M controllers.
However,many CS513 systems are still in operation worldwide.
Migration paths include:
Emulation via ABB Symphony Plus with ACE(Advanced Controller Emulator)
Replacement with AC 800M using logic conversion tools
Use of gateways to integrate with modern SCADA/PLC systems
ABB 5SHY4045L0006 3BHB030310R0001 3BHE039203R0101 GVC736CE101 5SHY4045L0006 3BHB030310R0001 3BHE039203R0101 GVC736CE101 ABB GRID BREAKER UNIT GBU72 3BHE055094R0002 3BHE031197R0001 3BHB030310R0001 In stock!!! Interested parties please inquire