Application Scenarios
In a large petrochemical refinery’s distributed control system, engineers faced a critical vulnerability: the single power supply feeding the Quantum PLC backplane was a single point of failure. If this unit failed, the entire process control loop would lose power, triggering an emergency shutdown costing millions in lost production. The solution was deploying two SCHNEIDER 140CPS11410 modules in a summable configuration at opposite ends of the Quantum backplane . This architecture allows the modules to share the load equally—each providing up to 8A for a combined capacity of 16A—and provides a true N+1 redundant power solution. When one SCHNEIDER 140CPS11410 required maintenance or failed, the other seamlessly sustained the full load, eliminating downtime and ensuring continuous operation of critical distillation column control.
Another typical application is in water treatment facilities where multiple I/O racks are deployed across a large plant. The SCHNEIDER 140CPS11410 provides reliable 5.1V logic power to the CPU and communication modules, while also supplying 24V DC to field devices through the backplane’s dedicated output pins . Its wide input range (93-276 VAC) and 47-63Hz frequency tolerance ensure stable operation even with fluctuating utility power common in remote pumping stations .
Parameters
| Main Parameters | Value/Description |
|---|---|
| Product Model | 140CPS11410 |
| Manufacturer | Schneider Electric (France) |
| Product Category | AC Power Supply Module, Modicon Quantum Series |
| Input Voltage | 115/230 VAC (Range: 93-138 VAC / 170-276 VAC) |
| Input Frequency | 47-63 Hz |
| Output Voltage | 5.1 VDC (to backplane) |
| Nominal Output Current | 8 A at 60°C; up to 10-11A in standalone configuration |
| Efficiency | 90% (typical) |
| Power Dissipation | 6.0 + (1.5 × I_OUT) W |
| Inrush Current | 38A @ 115VAC; 19A @ 230VAC |
| Input Protection | 2.0A slow-blow external fuse recommended |
| Protection Features | Overvoltage, overcurrent, short-circuit, thermal protection |
| Hot-Swap Support | Not hot-swappable; power off before insertion/removal |
| Redundancy Mode | Summable (N+1) with compatible modules; requires identical modules at opposite ends of backplane |
| Operating Temperature | 0°C to 60°C |
| Storage Temperature | -40°C to 85°C |
| Relative Humidity | 95% non-condensing |
| Weight | 0.55 – 0.91 kg (varies by configuration) |
| Dimensions (L×W×H) | Approx. 31.0 × 15.5 × 5.0 cm |
| Certifications | CE, UL, CSA, cULus, ATEX |
Technical Principles and Innovative Values
The SCHNEIDER 140CPS11410 distinguishes itself through its intelligent summable architecture, robust power conversion design, and comprehensive protection mechanisms.
- Innovation Point 1: Summable Architecture for N+1 Redundancy
The SCHNEIDER 140CPS11410 features a unique summable design that allows two identical modules to operate in parallel on the same Quantum backplane . When two units are installed—one at each end of the backplane—they share the load equally, providing combined capacity of 16A at 60°C . This architecture not only increases available power for high-density I/O configurations but also enables true N+1 redundancy. The system’s POK (Power OK) signal is generated by an internal AND logic gate, ensuring that the system is only considered powered-on if both internal POK signals are true . This dual-module approach increases the total system MTBF (Mean Time Between Failures) and distributes thermal load across the backplane, enhancing overall reliability. - Innovation Point 2: Wide Input Range and High Efficiency
The SCHNEIDER 140CPS11410 accepts an exceptionally wide AC input range—93 to 276 VAC—accommodating both 115V and 230V nominal systems without hardware configuration changes . This flexibility allows the same module to be used in diverse regional power grids (e.g., North America, Europe, Asia) without modification. With a typical conversion efficiency of 90%, the module minimizes energy loss and reduces heat generation within the control cabinet, lowering cooling requirements and operational costs . The 47-63Hz frequency tolerance further ensures stable operation on generator-supplied or unstable utility power common in industrial settings . - Innovation Point 3: Comprehensive Protection and System Diagnostics
The SCHNEIDER 140CPS11410 incorporates multiple layers of protection—overvoltage, overcurrent, short-circuit, and thermal—with response times as low as 10µs for fault conditions . The module’s front-panel LEDs provide visual status indication for power presence and fault conditions, while optional communication capability allows remote monitoring of power supply health through the Quantum system’s CRA module . The self-recovering fuse (5A) reduces maintenance requirements, automatically resetting after temporary overload conditions are cleared.







Reviews