Product Model: 190065A-01-01-01-00-00
Product Parameters:
- Brand: BENTLY (or Bently Nevada, a GE brand)12
 - Model: 1900/65A-01-01-01-00-00
 - 

190065A-01-01-01-00-00
 
Product Specifications:
- Inputs: Provides four sensor inputs and four temperature inputs3.
 - Sensor Support: Software can configure each sensor input to support 2-wire and 3-wire accelerometers, speed sensors, or proximity sensors3.
 - Outputs: Provides six relay outputs, four 4-20 mA recorder outputs, and one dedicated buffered output3.
 - Communication: Supports Modbus gateway option and Modbus communication via Ethernet and software-configurable RS232/485 serial ports4.
 - Power: Not specified in the search results, but generally Bently Nevada 1900/65A devices use 18 to 36 VDC5.
 - Display: Connected display (no cable)5.
 - Installation: DIN rail mount5.
 - Dimensions (approx.): 19.69 cm x 14.94 cm x 7.44 cm (length x width x height)3.
 - Weight (approx.): 8 kg5.
 - 

190065A-01-01-01-00-00
 
Features:
- Versatile Configuration: Software-configurable sensor inputs allow for flexibility in connecting different types of sensors3.
 - Multiple Outputs: Provides multiple outputs for various monitoring and control needs1.
 - Communication Options: Supports Modbus communication for easy integration into larger systems4.
 
Functions:
- Continuous Monitoring: Designed for continuous monitoring and protection of equipment used in various applications34.
 - Vibration Monitoring: Specifically, it can be used to monitor the vibration levels of rotating machinery, such as motors, pumps, and compressors2.
 - Alarming: Capable of generating alarms or notifications when abnormal conditions are detected6.
 - Data Recording: Likely has data recording capabilities to track historical performance data7.
 
Application Areas:
- Industrial Monitoring: Ideal for monitoring the condition of industrial equipment, including motors, pumps, compressors, and other rotating machinery236.
 - Preventive Maintenance: Helps predict potential equipment failures through continuous monitoring, enabling preventive maintenance strategies4.
 - Automation Systems: Can be integrated into larger automation systems through Modbus communication4.
 