Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | V18345-2010521001 |
| Manufacturer | ABB (Measurement & Analytics) |
| Product Family | TZIDC / TZID-C, V18345 ordering platform |
| Product Type | Intelligent electro-pneumatic valve positioner |
| Setpoint Input | 4–20 mA DC, two-wire, loop powered |
| Minimum Input Current | 3.6 mA (without analog feedback) |
| Load Voltage at 20 mA | 8.7 V DC (non-Ex version) |
| Input Impedance at 20 mA | Approx. 435 Ω |
| Local Communication | LCI adapter connector (non-hazardous areas only) |
| Explosion Protection | None (non-Ex configuration) |
| Pneumatic Action | Double acting |
| Power/Air-Loss Behaviour | Fail freeze – traps actuator pressure, holds last position |
| Supply Air Pressure | 1.4–6 bar (20–90 psi) |
| Output Pressure Range | 0–6 bar (0–90 psi) |
| Air Capacity | 5.0 kg/h at 1.4 bar; 13 kg/h at 6 bar |
| Steady Air Consumption | Below 0.03 kg/h |
| Position Sensing | Gearless non-contacting inductive travel sensor |
| Rotary Actuator Angle | 25–120° (optionally up to 270°) |
| Linear Actuator Angle | 25–60° |
| Travel Time Extension | 0–200 s per direction, independently adjustable |
| Dead Band / Tolerance Band | 0.1–10% / 0.3–10%, adjustable |
| Sampling Rate | 20 ms |
| Analog Position Feedback | Plug-in module, 4–20 mA, two-wire, separately powered |
| Digital Feedback Kit | Not fitted |
| Housing | Varnished die-cast aluminium with mechanical position indicator |
| Connections | Cable ½-14 NPT; air pipe ¼-18 NPT |
| Protection Rating | IP65 / NEMA 4X |
| Ambient Temperature | –40°C to +85°C |
| Vibration Resistance | 2 g at 300 Hz; 10 g up to 80 Hz |
| Weight | Approx. 1.7 kg |
| Mounting | Linear per DIN/IEC 534 / NAMUR; rotary per VDI/VDE 3845 |
Main Features and Advantages
Fail-freeze is the defining characteristic of the ABB V18345-2010521001. On loss of the 4–20 mA signal or electrical supply, this unit traps the existing actuator pressure and holds the valve at its last position instead of driving it to an end stop. That is exactly what a boiler attemperator spray valve, a steam turbine bypass or a compressor recycle line needs, because in those services both fully open and fully shut are themselves hazardous. Substituting a fail-safe or fail-freeze single-acting variant without engineering review changes the trip philosophy of the loop, not merely the hardware.Piezonic pilot construction keeps performance stable over time. The piezoelectric actuator in the ABB V18345-2010521001 has no sliding seals to wear and no orifice to clog, so hysteresis stays low, dead band remains adjustable down to 0.1%, and the 20 ms sampling loop holds position tightly even on sticky packing or ageing actuators. Steady-state consumption below 0.03 kg/h also reduces instrument-air load across a plant with hundreds of valves.Local commissioning removes dependence on a handheld. A single button starts Autoadjust on the ABB V18345-2010521001, the valve cycles, end stops are learned, and the adaptive controller tunes itself. Split range, characteristic curve, travel limits and travel-time extension are then set from the four-button panel, and the LCI port is available for a laptop where a full parameter record is required.Diagnostics support a move toward condition-based maintenance. The ABB V18345-2010521001 monitors signal range, travel deviation, positioning timeout, supply pressure and controller activity, and it totalises valve movements and cumulative travel. Setting alarm limits on those counters lets maintenance teams plan packing and seat work before a valve fails in service.