Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1746-BAS |
| Alternate Designation | 1746-BAS-A (hardware revision) |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Series | SLC 500 |
| Module Type | BASIC Language Co-Processor Module |
| Programming Language | BASIC-52 dialect (enhanced) |
| Memory | 24 KB battery-backed RAM |
| Optional Memory | 1747-M1 (8 KB EEPROM) / 1747-M2 (32 KB EEPROM) |
| Communication Ports | PRT1, PRT2 (serial), PRT3 (DH-485) |
| Serial Standards | RS-232/423, RS-422, RS-485 |
| Baud Rates | 300, 600, 1200, 2400, 4800, 9600, 19200 bps |
| DF1 Protocol Support | Yes, on PRT2 (full- or half-duplex) |
| Backplane Data Exchange | 8 input words / 8 output words |
| Real-Time Clock | Battery-backed, ±1 min/month at 25 °C |
| Backplane Current (5V DC) | 150 mA |
| Backplane Current (24V DC) | 40 mA (module only) |
| Diagnostic Indicators | 8 LEDs: ACT, 485, PRT1, PRT2, FAULT, BAT LOW, LED1, LED2 |
| Development Software | 1747-PBASE (MS-DOS environment) |
| Dimensions (H × W × D) | 130 × 80 × 26 mm (approx. 5.08 × 3.15 × 1.02 in) |
| Weight | Approx. 0.24…0.29 kg |
| Operating Temperature | 0…+60 °C (32…140 °F) |
| Storage Temperature | -40…+85 °C (-40…+185 °F) |
| Relative Humidity | 5…95%, non-condensing |
| Noise Immunity | NEMA ICS 2-230 |
| Vibration | 0.015 in p-p at 5…57 Hz; 2.5 g at 57…2000 Hz |
| Operating Shock | 30 g |
| Certifications | cULus Listed, CE, C-Tick, Class I Div 2 Groups A/B/C/D |
| Product Status | Mature / discontinued (new surplus available) |
Main Features and Advantages
A complete high-level programming environment inside the chassis: The 1746-BAS is not merely a communication adapter; it is a self-contained computer running an enhanced BASIC-52 interpreter. Engineers can write programs that perform floating-point mathematics, manipulate strings, format reports, and implement custom handshaking sequences—tasks that would be awkward or impossible in ladder logic. The integrated text editor and debugging environment allow programs to be developed, tested, and modified without leaving the industrial environment.Three independent communication pathways: With PRT1, PRT2, and the DH-485 port, the 1746-BAS can simultaneously talk to a local serial device, maintain a modem or DF1 link to a remote site, and participate in the plant DH-485 network. PRT1 is dedicated to user devices, while PRT2 supports DF1 protocol for remote programming, troubleshooting, and data transfer to other DF1 devices. The DH-485 port, connected through a 1747-AIC link coupler, lets the module function as a remote terminal unit on a network of SLC 500 processors.Battery-backed memory and real-time clock: The 24 KB RAM retains both program and data through power outages, while the onboard clock/calendar timestamps events and schedules report generation. Optional 1747-M1 and 1747-M2 EEPROM modules provide non-volatile storage for user programs and data that must survive battery failure—an important consideration for critical data-logging duties.Direct backplane integration for seamless data exchange: Because the 1746-BAS occupies a standard chassis slot, it exchanges data with the SLC 500 processor through the 1746 backplane rather than over a serial cable. This provides 8 input words and 8 output words of shared data, allowing the BASIC program to read process values and write results back into the controller’s data table without any external wiring.Industrial-grade reliability and hazardous-location approval: Built to NEMA noise-immunity standards and rated for 0…60 °C operation, the 1746-BAS survives the electrical noise, vibration, and shock of factory-floor duty. Its cULus Listing and Class I Division 2 approval mean it can be installed in cabinets serving hazardous locations without additional certification work.







Reviews