Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 990-05-XX-01-CN |
| Manufacturer | Bently Nevada (Baker Hughes) |
| Product Type | Two-wire, loop-powered vibration transmitter with integrated Proximitor sensor |
| Full-Scale Range (05 option) | 0-5 mils pp (0-125 µm pp) shaft relative vibration |
| System Length (XX option) | Configurable; 50 = 5.0 m (16.4 ft), 70 = 7.0 m (23.0 ft) total electrical length |
| Mounting Option (01) | 35 mm DIN-rail clips (02 = bulkhead mounting screws) |
| Agency Approval (CN) | China-region approval and CN connector configuration |
| Input Sensor | One non-contacting 3300 NSv proximity probe with matched extension cable |
| Output Signal | 4-20 mA DC proportional to peak-to-peak vibration, two-wire configuration |
| Supply Voltage | +12 to +35 V DC at the transmitter terminals |
| Maximum Loop Resistance | 1,000 Ω including cable at 35 V DC; Rloop = (Vsupply − 12 V) / 0.02 A |
| Loop Accuracy | ±1.5 % of full scale, measured from the TEST input across a 250 Ω loop |
| Frequency Response | 5 Hz to 6,000 Hz (+0, −3 dB) on the buffered output |
| Buffered Output | PROX OUT and COM terminals plus coaxial connector, 7.87 mV/µm (200 mV/mil) typical, 10 kΩ |
| Probe Gap for Valid Measurement | 0.5 mm to 1.75 mm (20 to 55 mils) from the target surface |
| Fault Behaviour | Not OK / Signal Defeat drives output below 3.6 mA within 100 µs; power-up inhibit 2-3 s |
| Operating Temperature | −35 °C to +85 °C (transmitter); probe rated −52 °C to +177 °C |
| Storage Temperature | −52 °C to +100 °C |
| Humidity | 100 % condensing, non-submerged, potted construction |
| Housing / Protection | Aluminium, potted, IP66 / NEMA 4X class enclosure |
| Dimensions | Approx. 100.1 × 73.9 × 53.3 mm |
| Weight | Transmitter 0.43 kg; total system approx. 0.82 kg |
| Country of Origin | United States |
Main Features and Advantages
Integrated Proximitor electronics remove a whole box from the design: The Bently Nevada 990-05-XX-01-CN carries the proximity driver inside the transmitter housing, so there is no separate Proximitor unit to buy, mount, wire or calibrate. For an OEM building a compressor skid, that is one less part number, one less enclosure penetration and one less failure point in the loop.A signal every control system understands: By outputting a standard 4-20 mA current proportional to peak-to-peak vibration, the Bently Nevada 990-05-XX-01-CN talks directly to any PLC analog input, DCS card or alarm relay without gateways or proprietary modules. Commissioning teams can scale the loop in engineering units in minutes.Signal Defeat logic prevents false trips: A failing probe or a loose connector is one of the most common causes of spurious machinery alarms. The Bently Nevada 990-05-XX-01-CN detects the Not OK condition and drives the loop below 3.6 mA within 100 microseconds rather than pushing the output high, so a broken transducer reports as a fault instead of pretending the machine is shaking apart.Buffered output keeps diagnostics possible: PROX OUT and COM terminals plus a coaxial connector give access to the raw dynamic vibration and gap voltage at 200 mV/mil. Technicians can clip on a portable analyzer to check the actual waveform. Because this output is not isolated from the loop, the 990/991 Test Adapter is strongly recommended whenever AC-powered test equipment is used.Calibration and verification without dismantling: Non-interacting zero and span potentiometers sit under the transmitter label, and a Test Input pin lets you inject a function generator signal and verify the whole loop end to end. That turns loop checking into a five-minute task during a shutdown.Built for wet, cramped and hostile locations: The potted construction tolerates 100 % condensing humidity, the aluminium housing is rated IP66 / NEMA 4X, and the compact footprint along with the NSv probe’s small tip fits installations where clearance is minimal.
Application Field
Centrifugal air compressors and blowers are the design target for the Bently Nevada 990-05-XX-01-CN. These machines usually ship with an OEM control panel that needs one overall vibration value for alarm and shutdown logic. The transmitter delivers exactly that over a single twisted pair, which keeps panel wiring simple and lets the OEM ship a monitored package without engineering a protection rack.Small pumps, motors and fans are the second broad use case. Plants with dozens of general-purpose machines cannot justify a 3500 rack per unit, but they still want trending data that flags imbalance, loosening or bearing wear before failure. The Bently Nevada 990-05-XX-01-CN provides that trend signal into the existing DCS historian, so mechanical problems show up as a rising milliamp value long before an operator hears anything unusual.Retrofit and brownfield work is where the economics are most attractive. When an old machine has a failed eddy-current driver or a legacy monitor that no longer has spares, replacing the chain with a Bently Nevada 990-05-XX-01-CN and an NSv probe restores a working vibration signal into the modern control system at a fraction of a rack replacement cost.Water and wastewater, HVAC utility skids, and remote unmanned pump stations also use this transmitter because the 4-20 mA loop tolerates long cable runs and the potted housing survives wet, condensing environments.One boundary deserves emphasis: the Bently Nevada 990-05-XX-01-CN provides overall amplitude trending, not machinery diagnostics. It cannot determine vibration phase, and it does not capture dynamic waveforms at the moment of an alarm. For critical turbomachinery requiring API 670 protection, specify a 3500 monitoring system instead, and use the transmitter for the balance of plant.