| Product Model |
991-01-50-01-00 (internal part 288865-01) |
Order by the full code; the internal number appears on some labels and test reports |
| Manufacturer |
Bently Nevada (Baker Hughes) |
Original equipment manufacturer, USA origin |
| Product Category |
Axial position (thrust) transmitter, 2-wire loop-powered, with integrated Proximitor |
Signal conditioner and transmitter in one box; no separate Proximitor unit needed |
| Input |
1 × 3300 NSv non-contacting proximity probe with matching extension cable |
Must be NSv type – an 8 mm 3300 XL probe will not tune correctly with this transmitter |
| System Length Option (50) |
5.0 m (16.4 ft) total calibrated length |
Probe plus extension cable must add up to 5 m; mixing in a 7 m set causes real calibration error |
| Full-Scale Option (01) |
Code not listed in the current official ordering table (which offers 06 = 0.6-0-0.6 mm and 25 = 25-0-25 mils); platform measures up to 1.2 mm (50 mils) total thrust travel |
Confirm the actual range on the unit nameplate before ordering a replacement, so the PLC scaling stays correct |
| Power Requirement |
+12 to +35 Vdc at the transmitter terminal |
Runs straight off a standard 24 V loop supply; no separate power wiring |
| Output Signal |
4 to 20 mA DC, proportional to axial position, 2-wire |
Universal control system input; alarm logic lives in the PLC or DCS |
| Loop Accuracy |
Within ±1.5% of full scale (typical), rated across a 250 Ω loop resistance |
Good enough for alarming and trending; not a substitute for a dynamic monitoring system |
| Maximum Loop Resistance |
1,000 Ω including cable at 35 Vdc |
At 24 V supply, keep cable runs reasonable or verify loop budget during design |
| Not OK / Signal Defeat |
Output drops below 3.6 mA within 100 µs of a fault; restores within 0.1 s after the fault clears |
A broken probe or loose connector drives the loop to a safe low value instead of a false high reading |
| Zero and Span |
Non-interacting external potentiometers under the transmitter label |
Adjusting span does not disturb zero, so loop calibration takes one pass |
| PROX OUT Diagnostic Output |
Non-isolated dynamic vibration and gap voltage, 7.87 mV/µm (200 mV/mil) ±6.5%, 10 kΩ source impedance |
Lets a technician see the raw gap voltage and vibration; requires the 122115-01 adapter with AC-powered instruments |
| Mounting Option (01) |
35 mm DIN-rail clips |
Clips straight into a control cabinet rail; bulkhead screw variants (02/03) exist for panel mounting |
| Agency Approval (00) |
Not required |
Safe/general-purpose areas only; choose 01 or 05 suffixes where CSA Div 2 or ATEX is needed |
| Environmental Limits |
Operating -35 °C to +85 °C; storage -51 °C to +100 °C; 100% condensing humidity, non-submerged |
Potted construction suits humid compressor halls and outdoor skids |
| Weight / Dimensions |
0.43 kg transmitter, approx. 0.82 kg total system; 100.1 × 73.9 × 53.3 mm |