Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 269PLUS-D/O-211-100P-HI |
| Manufacturer | GE Multilin (General Electric / GE Vernova Grid Solutions) |
| Product Type | Digital Motor Management and Protection Relay |
| Case Style | D/O drawout version (withdrawable without disturbing wiring) |
| Phase CT Input | 5 A secondary (code 2) |
| Ground CT Input | 5 A secondary (code 2) |
| Control Power | 90-300 V DC / 80-265 V AC, 50/60 Hz (HI range) |
| RTD Inputs | Up to 10 programmable 100 Ω platinum (Pt100) RTDs, 3-wire |
| Digital Inputs | 5 programmable (spare, differential relay, speed switch, external reset, emergency restart) |
| Output Relays | 4 (trip, alarm, auxiliary 1, auxiliary 2); code 1 arrangement: N.O. contacts |
| Failsafe Code | 1 (Trip FS, Alarm NFS, Aux1 NFS, Aux2 FS) |
| Analogue Output | 1 programmable 4-20 mA output |
| Communication | RS-485, Modbus RTU (Profibus-DP on selected variants) |
| Display and Interface | 48-character alphanumeric LCD, keypad, status LEDs |
| Protection Functions | Thermal overload, short circuit, ground fault, unbalance/single phasing, locked rotor, stall, undercurrent, RTD overtemperature, starts-per-hour, restart inhibit |
| Thermal Model | I²t thermal capacity used (%TCU), RTD bias, true exponential cooldown, non-volatile thermal memory |
| Metering | 3-phase current, ground current, thermal capacity used, start count, run hours |
| Frequency Range | 50/60 Hz nominal; 15-300 Hz for VFD-fed motors |
| Operating Temperature | -25 °C to +60 °C |
| Dimensions (W x H x D) | Approx. 193 x 125 x 290 mm (verify against unit nameplate) |
| Weight | Approx. 3.5-5.0 kg depending on case and options |
| Mounting | Panel / switchgear flush mount |
| Certifications | UL, CE, CSA |
Main Features and Advantages
Thermal modeling that reflects the real machine: The defining capability of the GE Multilin 269PLUS-D/O-211-100P-HI is its thermal model. Rather than inferring winding temperature from current alone, it calculates I²t thermal capacity used and then validates that figure against actual stator temperature measured by up to ten 100 Ω platinum RTDs, always acting on the higher of the two values. This means a motor that is overheating because of lost cooling, blocked ventilation or an extreme ambient condition is protected just as effectively as one drawing excess current. A dual-slope RTD bias curve lets the relay be matched to the specific hot and cold damage curves of the machine.True exponential cooldown: Motor cooling is not linear, and the GE Multilin 269PLUS-D/O-211-100P-HI models it as a genuine exponential decay. Because the initial cooling rate is steep, the relay permits more frequent load cycling than a linear model would allow, increasing usable throughput on cyclic duty without eroding insulation life. Non-volatile thermal memory means that after a control power interruption the relay resumes from the correct thermal state rather than assuming a cold machine, closing a classic protection gap.Drawout construction for live-cabinet service: The withdrawable case allows the GE Multilin 269PLUS-D/O-211-100P-HI to be removed, tested or swapped with field terminations untouched. For plants that cannot afford extended outages, this turns what would be a rewiring job into a short, controlled intervention.Diagnostics that reduce maintenance guesswork: The 48-character display, stored statistics and trip records give technicians immediate visibility of why a motor stopped. Built-in self-checking of relay circuitry, tamperproof setpoints in non-volatile memory, and optional RS-485 Modbus RTU integration mean the same data is available locally at the switchgear and remotely in the control room. FlexCurve custom overload curves and an emergency restart function add the flexibility needed for process-critical drives.
Application Field
In power generation, the GE Multilin 269PLUS-D/O-211-100P-HI protects the auxiliary motors that keep a station running: boiler feed pumps, induced and forced draft fans, condensate pumps, coal and ash handling conveyors. Losing one of these auxiliaries can derate or trip a unit, so the combination of thermal modeling, start supervision and detailed trip records directly supports availability targets.Oil, gas and petrochemical facilities apply the GE Multilin 269PLUS-D/O-211-100P-HI to compressors, pump motors and fin-fan coolers where motors are large, duty is continuous, and a winding burn-out represents both a major capital loss and a long lead-time replacement. Ground fault detection, unbalance protection and bearing RTD monitoring catch the failure modes that develop over months rather than seconds.Water and wastewater utilities value the relay on high-cycle pump duty. Frequent starts are exactly the duty that destroys motors through accumulated starting heat, and the starts-per-hour supervision plus restart inhibit functions in the GE Multilin 269PLUS-D/O-211-100P-HI manage that exposure automatically while preserving the operational flexibility operators need during storm or peak-demand events.Mining, cement and minerals operations use it on high-inertia loads such as ball mills, kiln drives, crushers and long conveyors, where acceleration times are long and locked-rotor protection must be carefully coordinated. Pulp, paper, chemical and marine installations specify the same device for refiners, agitators and deck machinery, and because the relay is proven on variable frequency drive outputs from 15 to 300 Hz, it suits retrofits where fixed-speed motors have been converted to variable speed control.
Related Products
269PLUS-SV-100P-HI — Standard, non-drawout version of the same relay with identical 100 Ω platinum RTD and high-range control power; chosen where withdrawable construction is not required and panel depth is limited.269PLUS-D/O-211-100P-LO — Same mechanical and I/O configuration as the 269PLUS-D/O-211-100P-HI but with the low-range control supply (20-60 V DC / 20-48 V AC) for stations fed from battery-backed DC systems.269PLUS-D/O-211-10C-HI — Variant specified with 10 Ω copper RTDs instead of platinum; used when matching existing motor-embedded copper detectors rather than replacing them.269PLUS-D/O-211-100N-HI — 100 Ω nickel RTD version, supplied to match legacy North American motor winding detectors.269PLUS-D/O-121-100P-HI — Same relay with a 2000:1 zero-sequence ground CT (50:0.025 A) instead of 5 A, intended for high-resistance grounded systems where sensitive earth fault detection is required.269PLUS-D/O-311-100P-HI — 1 A phase CT variant, selected where switchgear is already equipped with 1 A secondary current transformers.SR469-P5-HI-A20-E — GE Multilin 469 motor management relay, the modern migration target when a 269 Plus installation is being upgraded rather than maintained.489-P5-HI-A20-T — GE Multilin 489 relay, specified where combined generator and motor protection is needed in the same device.EnerVista 269 / 269PC software — Windows-based setup and monitoring package used to configure setpoints, download event records and commission the 269PLUS-D/O-211-100P-HI from a laptop.