Technical Specifications
Product Model:HIMA Z7306
Manufacturer:HIMA
Product Type:Digital Output Module
Series:HIMatrix
Number of Channels:16 digital outputs
Nominal Voltage:24 VDC
Output Current:0.5 A per channel
Rated Load:2.5 A(all channels combined)
Short-Circuit Protection:Yes
Reverse Polarity Protection:Yes
Built-in Diagnostics:Yes(monitors for open circuits and short circuits)
Safety Integrity Level(SIL):Up to SIL 3 in accordance with IEC 61508
Ex Marking:EEx nA IIC T4,suitable for use in Zone 2 hazardous areas
Operating Temperature:-25°C to+70°C
Ingress Protection(IP):IP 20
Key Features and Advantages
High Safety Integrity:The HIMA Z7306 is certified for use in applications up to SIL 3,which is the highest level of functional safety for a single module.This certification confirms its robust design and reliability in preventing dangerous failures.Its built-in diagnostics continuously check for faults like open circuits and short circuits,immediately flagging any issues to the control system.
Redundancy and Reliability:While the module itself is single-channel,it is designed to be integrated into redundant systems.The HIMatrix platform supports redundant CPUs and communication modules,ensuring that even if one component fails,the system remains operational.This feature is vital in critical applications where a single point of failure is unacceptable.
Ease of Integration:The HIMA Z7306 is part of a modular system,making it easy to install and integrate into new or existing control panels.Its compact design saves valuable cabinet space,and the simple screw-terminal connections simplify field wiring.The module’s full compatibility with the HIMatrix series ensures a seamless and hassle-free setup process.
Application Areas
The HIMA Z7306 is predominantly found in industries where safety is the top priority.
Oil and Gas:Used in Emergency Shutdown Systems(ESD),Fire and Gas(F&G)systems,and Burner Management Systems(BMS)to safely shut down processes or activate alarms.
Chemical Plants:Deployed to control safety-critical valves and pumps,preventing runaway reactions and containing hazardous materials.
Power Generation:Utilized in turbine control and generator protection systems to ensure safe operation and prevent equipment damage.
Railways:Employed in railway signaling and interlocking systems to control track switches and signals,ensuring train safety.
Installation and Maintenance
Installation:Before installing the HIMA Z7306,make sure the power to the HIMatrix rack is completely turned off.The module is designed for simple”click and snap”installation onto the backplane.Ensure that the module is firmly seated in its slot to guarantee a reliable connection.Always follow the wiring diagrams provided in the manual to connect field devices to the screw terminals.
Maintenance:The HIMA Z7306 is a low-maintenance component.Its self-diagnostic capabilities reduce the need for manual checks.However,periodic visual inspections are recommended to ensure all connections are secure and there is no physical damage.In the event of a fault,the diagnostic LED on the module will indicate the issue,allowing for quick and efficient troubleshooting.If a module requires replacement,it can be easily swapped out with a new one,minimizing downtime.
ABB 5SHY4045L0006 3BHB030310R0001 3BHE039203R0101 GVC736CE101 5SHY4045L0006 3BHB030310R0001 3BHE039203R0101 GVC736CE101 ABB GRID BREAKER UNIT GBU72 3BHE055094R0002 3BHE031197R0001 3BHB030310R0001 In stock!!! Interested parties please inquire

Reviews