Woodward IRI1-I5E05D Microprocessor Earth Fault Relay缩略图

Woodward IRI1-I5E05D Microprocessor Earth Fault Relay

Woodward IRI1-I5E05D Microprocessor Earth Fault Relay插图

 

Product Overview

The Woodward IRI1-I5E05D​ is a high-performance microprocessor-based earth fault (ground fault) protection relay, designed to deliver highly sensitive ground fault detection and reliable protective tripping for industrial AC power systems. As a core member of the Woodward IRI relay protection family, the Woodward IRI1-I5E05D​ operates on the residual (zero-sequence) current principle, continuously monitoring leakage current through neutral grounding, busbars, generator star points, and transformer windings to identify even very low-level insulation breakdowns that conventional overcurrent devices cannot see. Its role is critical in preventing arc flash, equipment burnout, and uncontrolled earth faults in generators, transformers, motors, and switchgear.Engineered around a fast digital signal processor, the Woodward IRI1-I5E05D​ applies Discrete Fourier Transform (DFFT) filtering to suppress harmonics, DC components, magnetizing inrush, and out-of-zone unbalanced currents, thereby avoiding false tripping during transient disturbances. The relay conforms to ANSI device functions 50N/51N and supports both definite-time and inverse definite minimum time (IDMT / IEC 60255) characteristics, allowing it to coordinate correctly with upstream and downstream protective devices. With a 5 A nominal CT secondary input, a wide-range 230 V AC/DC auxiliary supply, and a configurable 0.05–5 A operating threshold, the unit adapts to solidly grounded, resistance-grounded, and high-resistance grounded networks alike.The Woodward IRI1-I5E05D​ is built for demanding industrial service. Its compact withdrawable housing supports DIN rail, panel, door, and 19-inch rack mounting, while the front face carries an IP54-rated sealed operator interface with multi-colour LEDs for power, ready, fault type, trip, and alarm status. All settings are made locally through sealed DIP switches and internal jumpers—no software or commissioning laptop is required on site. This combination of laboratory-grade measurement accuracy, field-programmable flexibility, and rugged industrial construction makes the Woodward IRI1-I5E05D​ a dependable, long-service-life choice for critical earthing protection.

 

Technical Specifications

Parameter Name Parameter Value
Product Model IRI1-I5E05D​
Manufacturer Woodward
Product Type Microprocessor Earth Fault (Ground Fault) Protection Relay
Protection Functions ANSI 50N / 51N sensitive earth fault, zero-sequence overcurrent
Rated CT Secondary Current 5 A (model suffix I5; 1 A version also available in series)
Operating Threshold Range 0.05 – 5 A (CT secondary side), DIP-switch selectable
Time Characteristics Definite-time 0.05–10 s; IDMT inverse-time per IEC 60255
Filtering / Algorithm DFFT digital filtering, harmonic & DC component rejection
Auxiliary Supply 230 V AC/DC universal (110 V versions available in series)
Output Contacts 2 × SPDT (Form C), 250 V AC / 5 A and 30 V DC / 5 A
Front Panel Indication Power, Ready, Earth Fault, Trip, Alarm LEDs + RESET button
Reset Modes Auto-reset after fault cleared; manual via panel button or external dry contact
Measurement Input Burden ≤ 0.2 VA per CT input
Frequency Compatibility 50 Hz / 60 Hz (DIP-selectable)
Mounting DIN rail / panel / door / 19-inch rack, withdrawable chassis
Dimensions (H × W × D) 260 × 72 × 138 mm
Weight Approx. 1.0 kg
Operating Temperature −20 °C to +60 °C
Storage Temperature −40 °C to +85 °C
Humidity 5 – 95 % RH, non-condensing
Enclosure Protection Front panel IP54; internal wiring side IP20
Standards & Certifications CE, UL, IEC 60255, Class I Division 2