Honeywell 900B01-0101 Analog Output Module for ControlEdge HC900 Process Controllers缩略图

Honeywell 900B01-0101 Analog Output Module for ControlEdge HC900 Process Controllers

Honeywell 900B01-0101 Analog Output Module for ControlEdge HC900 Process Controllers插图

 

Technical Specifications

Parameter Name Parameter Value
Product Model 900B01-0101
Manufacturer Honeywell International Inc.
Product Type Analog Output Module (AO), 4-channel, galvanically isolated
Series / Platform Honeywell ControlEdge HC900 / 900 Series hybrid control system
Number of Outputs 4 individually isolated channels
Output Signal Range 0 to 21.8 mA per channel, user-scalable (typically configured 4-20 mA)
Accuracy ±0.1% of full scale under reference conditions
D/A Resolution 12 bits
Maximum Load Resistance 750 Ω per channel
Galvanic Isolation 500 VDC channel-to-channel; 600 VDC field-to-logic
Minimum Detectable Current > 3.5 mA per output for output-current verification
Failsafe Behaviour User-specified failsafe value per channel on loss of communication
Rate Control User-specified rate-of-change limit and synchronous output updates
Backplane Power Consumption 5 VDC at 40 mA maximum; 24 VDC at 200 mA maximum
Diagnostics Factory and field calibration monitoring, configuration checks, 24 VDC supply supervision, output current feedback
Calibration Storage Non-volatile memory with redundant factory calibration and per-channel field calibration
Modules per Rack Up to 10 standard, up to 12 with temperature de-rating
Operating Temperature 0 °C to +60 °C (storage −40 °C to +85 °C)
Relative Humidity 5% to 95% non-condensing
Dimensions (H × W × D) 137 × 35.6 × 137.16 mm
Weight Approx. 0.397 kg
Certifications CE, UL listed for industrial control equipment, RoHS compliant

 

Main Features and Advantages

True per-channel isolation: The Honeywell 900B01-0101​ isolates all four outputs from each other and from the logic side, which eliminates the ground loops and cross-talk that plague non-isolated output cards. In practical terms, a technician can break a loop, short a cable or replace an actuator on channel 3 without disturbing channels 1, 2 and 4, and without risking the controller backplane. This is especially valuable in plants where several control valves share a common pipe rack, a common cable tray and a common earthing system.Output verification that closes the loop: Many analog output cards are “write-only”: the controller sends a value and hopes the field device received it. The Honeywell 900B01-0101​ senses the actual current flowing in each loop and reports it back, so the control strategy can raise an alarm when a valve coil opens, a loop wire breaks or an actuator input fails. Combined with continuous monitoring of calibration, configuration and the 24 VDC field supply, this turns a silent failure into a visible, diagnosable event.Predictable behaviour under fault conditions: Every channel of the Honeywell 900B01-0101​ can be assigned its own failsafe value, so when communication with the controller is interrupted the outputs move to a defined safe position rather than freezing at the last command or drifting to an unknown level. Programmable rate-of-change limits prevent a setpoint step from slamming a valve or jerking a damper, and synchronous output updates guarantee that all four channels change on the same controller scan, which matters for ratio and cascade strategies.Service-friendly by design: Factory calibration is stored redundantly, invalid versions are rejected automatically, and individual channels can be field-calibrated with the results retained through power loss. The Honeywell 900B01-0101​ supports insertion and removal under power in an HC900 rack, and dual status LEDs give instant front-panel confirmation: a blinking green LED indicates normal scanning, while a red LED flags a module or channel fault. With up to ten modules per rack and rack expansion via I/O scanners, output capacity grows with the process rather than forcing a platform change.