ABB 1MRK002239-BBR01 SR91C790 Power Supply Module – 24 V DC Stabilized PSU for Relion 670 / Protection Racks缩略图

ABB 1MRK002239-BBR01 SR91C790 Power Supply Module – 24 V DC Stabilized PSU for Relion 670 / Protection Racks

ABB 1MRK002239-BBR01 SR91C790 Power Supply Module – 24 V DC Stabilized PSU for Relion 670 / Protection Racks插图

 

Description:

The ABB 1MRK002239-BBR01, also referenced by its type code SR91C790, is a rack-mount Power Supply Module (PSM — Power Supply Module / Protection System Module) manufactured by ABB for use in ABB Relion® 670 series Intelligent Electronic Devices (IEDs), protection relay subracks, and certain DCS/automation backplanes. It converts a wide-range AC or DC input (typically 110–250 V DC / 85–264 V AC) into regulated internal DC rails—commonly +5 V, ±12 V, and +24 V—to power the processor, communication cards, and binary I/O modules housed in the same rack, with galvanic isolation and built-in overload protection.

Application Scenarios:

In a 220 kV substation, a RED670 line differential protection IED suddenly went dark during a routine secondary system inspection—traced to a failed rack power supply that had been in service for 18 years. Because the station battery voltage (220 V DC) fluctuates during switching operations, the replacement unit must tolerate wide input swings and provide clean, isolated DC to the sensitive protection electronics. The maintenance team installed the ABB 1MRK002239-BBR01 (SR91C790)​ as a direct like-for-like swap into the dedicated PSM slot of the Relion 670 rack. The module accepted the 220 V DC station battery without adjustment, locked into the backplane, and the IED booted normally within seconds—all binary status LEDs confirming “Power OK.” The wide-input tolerance and >40 ms ride-through capability of the 1MRK002239-BBR01​ now protect the IED from momentary battery sags during breaker closing, directly addressing the pain point of unexplained protection-drop events during heavy switching operations.

 

Parameter:

Main Parameters Value/Description
Product Model 1MRK002239-BBR01​ (Type: SR91C790)
Manufacturer ABB (Sweden / Power Systems / Protection & Control Division)
Product Category Rack-Mount Power Supply Module (PSM) for Relion 670 / Protection Subrack
Input Voltage 110–250 V DC (typical BBR version) / 85–264 V AC (auto-ranging, 47–63 Hz)
Output Rails Regulated multi-rail DC — typically +5 V, +12 V, –12 V, +24 V (internal backplane distribution)
Output Power Approx. 40–60 W total (sufficient for processor + comm + I/O cards in one IED rack)
Ride-Through Time > 40 ms @ nominal input (bridges brief DC bus dips)
Galvanic Isolation Input–Output ≥ 1500 V AC (per IEC 60255), protects sensitive backplane electronics
Protection Features Overcurrent, short-circuit, overvoltage, overtemperature; internal fail contact / signal
Status Indication Front-panel LED (Power OK / Fail) + optional “Internal Fault” relay contact to SCADA
Cooling / Enclosure Natural convection (fanless); metal-shielded plug-in module with locking screw
Mounting Method Dedicated PSM slot in ABB Relion 670 / 650 series rack or compatible protection subrack
Operating Temperature –40 °C to +70 °C (IEC 60255 grade for substation environments)
Dimensions (approx.) 138 × 60 × 15 mm (H × W × D); Weight ≈ 0.20–0.35 kg
Certifications CE, cULus, IEC 60255 EMC/Insulation compliant, RoHS

 

Technical Principles and Innovative Values:

  • Innovation Point 1: Wide DC/AC Input with Ride-Through for Substation Battery Systems.​ The ABB 1MRK002239-BBR01​ is specifically engineered to accept the typical 110 V DC or 220 V DC station battery supply—as well as universal AC—and includes bulk capacitance for >40 ms hold-up during switching transients, preventing nuisance IED resets that plague generic switched-mode supplies in switchyards.
  • Innovation Point 2: Multi-Rail Regulated Outputs with Galvanic Isolation.​ Unlike a simple 24 V DC brick PSU, the SR91C790​ generates and stabilizes all the internal voltage rails (+5 V logic, ±12 V analog/I/O, +24 V auxiliary) required by the rack’s mixed-signal cards, with full galvanic isolation from the station battery—protecting sensitive A/D converters from ground-loop-induced noise.
  • Innovation Point 3: Backplane Integration & Self-Diagnostics with Fail Signaling.​ The module plugs directly into the system backplane and is recognized by the IED firmware. An internal watchdog monitors output regulation; if an undervoltage or overtemperature condition occurs, the front LED changes state and a dry-contact / logic-level “Internal Fault” signal can be wired to the station DC & S system—turning a silent PSU failure into a logged alarm before the IED loses power.