ABB 1MRK002247-AH Measurement Board: Burden-Optimized CT/VT Inputs with Galvanic Isolation缩略图

ABB 1MRK002247-AH Measurement Board: Burden-Optimized CT/VT Inputs with Galvanic Isolation

ABB 1MRK002247-AH Measurement Board: Burden-Optimized CT/VT Inputs with Galvanic Isolation插图

Description

The ABB 1MRK002247-AH​ is an internal Current / Voltage Transformer (CT/VT) analog input conditioning module—also referred to as a measurement or analog front-end board—designed for installation inside ABB REx670 series numerical protection and control IEDs (REG670, REL670, RET670, REC670). It receives secondary currents from protective CT cores (typically 1 A or 5 A) and secondary voltages from VT/PT secondaries (typically 100 V / 110 V line-to-line or 57.7 V phase-to-neutral), scales and filters them, and presents precision analog signals to the relay’s main A/D conversion stage. The 1MRK002247-AH​ typically supports six CT inputs and two to four VT inputs depending on the relay variant and is a fundamental component for accurate phasor measurement, metering, fault recording, and protection-element operation.h2 Application ScenariosImagine a 220 kV transmission substation where an ABB REG670 distance-protection relay begins reporting slightly skewed apparent-power values and occasional “Metering Channel Error” self-test warnings after years of service. Ratio checks confirm the primary CT/VT secondaries are correct—the issue is traced to aging burden resistors and filter capacitors on the internal analog-input board. Rather than replace the entire IED (which would necessitate reloading the SCL configuration, re-verifying protection settings, and scheduling a protection outage), the protection engineer sources a version-matched ABB 1MRK002247-AH (AH revision). With the DC and VT supplies isolated, the relay lid is opened, the old PCB is disconnected from its backplane header and standoffs, and the new 1MRK002247-AH​ is seated. On power-up the relay passes all self-tests; magnitude and phase-angle accuracy return to specification with no re-calibration required. This scenario illustrates the 1MRK002247-AH‘s vital function: it is the precision gateway between the switchyard analog world and the digital protection algorithm, and a targeted board swap restores measurement fidelity without disturbing commissioned logic.h2

 

Parameter

Main Parameters Value/Description
Product Model 1MRK002247-AH​ (AH Revision)
Manufacturer / Origin ABB / Switzerland (CH)
Product Category Internal CT / VT Analog Input Conditioning Module (Measurement Board)
Compatible Host Devices ABB REx670 series IEDs (REG670, REL670, RET670, REC670 — confirm host type & rear-slot layout)
CT Input Channels 6 × independent CT inputs (1 A or 5 A nominal secondary; selectable via host configuration / hardware jumper in some variants)
VT / PT Input Channels 2 × 3-phase VT (line-to-line 100/110 V) or 4 × VT (phase-to-neutral 57.7/63.5 V) — variant-dependent
Rated CT Burden ≤ 0.1 VA / ≤ 0.2 VA per phase (low-burden design to minimize CT saturation influence)
Frequency Range 50 / 60 Hz ± 5 Hz (extends to harmonic measurement range per relay firmware)
Isolation Galvanic isolation between analog inputs, logic section, and backplane (typ. ≥ 2000 V RMS test)
Analog Bandwidth DC to ≈ 2 kHz (covers fundamental + 2nd–5th harmonic for some protection elements)
Connectors Multi-pin header / card-edge to motherboard + screw-terminal or plug-in field terminals (host-dependent)
Operating Temperature -20 °C to +70 °C (per host IED specification)
Mounting Method Plug-in mount on internal chassis / motherboard inside REx670 relay housing

 

*Note: Exact CT/VT channel count, 1 A / 5 A selection method, and terminal block type must be verified against the removed board photo and host device nameplate before ordering.h2 Technical Principles and Innovative ValuesThe 1MRK002247-AH​ is a precision analog front-end—not a standalone meter—engineered to stringent protection-class accuracy requirements.

  • Innovation Point 1 – Low-Burden Wide-Range CT Inputs: The 1MRK002247-AH​ uses precision shunt resistors and active buffering to present a very low burden (≤ 0.1–0.2 VA @ 1 A / 5 A) to the CT secondary. This minimizes the risk of CT saturation during high-fault currents and preserves waveform fidelity for sensitive elements such as sensitive directional comparison and harmonic restraint functions.
  • Innovation Point 2 – Anti-Aliasing Filtering with Phase-Shift Compensation: Each CT and VT channel incorporates a 2nd-order analog low-pass filter (fc ≈ 1.5–2 kHz) to prevent aliasing before A/D sampling, followed by digital phase-angle compensation in the relay firmware. This dual-stage approach yields Class 0.5 / Class 1 metering accuracy and ≤ ±0.5° phase error across the rated frequency band—critical for distance protection reach accuracy.
  • Innovation Point 3 – Transparent Swap with Auto-Calibration Recall: All ratio, vector-group, and phasor-correction coefficients are stored in the relay CPU’s non-volatile memory—not on the 1MRK002247-AH. On replacement, the relay performs an automatic self-calibration / sanity check at power-up and applies the saved correction factors, so measurement accuracy is restored without manual recalibration or re-entry of CT/VT ratios.