HIMA F7126 Galvanically Isolated Input Module – Supports Fail-Safe Wiring in Oil, Gas & Chemical Plants缩略图

HIMA F7126 Galvanically Isolated Input Module – Supports Fail-Safe Wiring in Oil, Gas & Chemical Plants

HIMA F7126 Galvanically Isolated Input Module – Supports Fail-Safe Wiring in Oil, Gas & Chemical Plants插图

Description

The HIMA F7126 is a 32-channel digital input(DI)module engineered for HIMA’s HIMax®safety PLC platform—a leading SIL 3-certified system used in high-integrity safety applications worldwide.Designed for integration into HIMax H41q,H51q,and H61q controller racks,the F7126 provides reliable acquisition of binary field signals such as limit switches,pushbuttons,valve feedbacks,motor starters,and fire/gas detector contacts.

Each input supports 24VDC sourced or dry-contact wiring,with galvanic isolation between field circuits and the internal logic bus,ensuring immunity to ground loops,surges,and electrical noise.The module features integrated wire-break detection(open-circuit monitoring)and short-circuit protection,critical for maintaining diagnostic coverage in safety instrumented functions(SIFs).

Certified to IEC 61508:2010(SIL 3)and IEC 61511,the F7126 is suitable for use in Emergency Shutdown(ESD),Burner Management Systems(BMS),High-Integrity Pressure Protection Systems(HIPPS),and machinery safety applications.It supports hot-swap replacement in redundant HIMax configurations,enabling maintenance without process interruption—a key requirement in continuous-operation industries.

Application Scenarios

At a North Sea offshore platform,a HIPPS system using HIMA HIMax H51q controllers relies on F7126 modules to monitor 256 pipeline pressure switch statuses.During a routine inspection,a corroded terminal caused an open circuit on one input.The F7126’s wire-break detection immediately triggered a diagnostic alarm(not a spurious trip),allowing technicians to repair the wiring during the next planned window—preventing an unnecessary$5M production shutdown while maintaining full safety integrity.

Parameter

Main Parameters Value/Description

Product Model F7126

Manufacturer HIMA Paul Hildebrandt GmbH+Co KG

Product Category Digital Input(DI)Module for HIMax Safety PLC

Compatible Controllers HIMax H41q,H51q,H61q(all firmware versions with I/O compatibility)

Number of Channels 32 independent digital inputs

Input Type

•24 VDC sourced input(current-sinking)

•Dry contact/passive switch(with external 24VDC supply)

Nominal Input Voltage 24 VDC±10%(19.2–28.8 VDC)

Input Current~3 mA per channel(at 24 VDC)

Input Filtering Adjustable debounce(software-configurable:0–50 ms)

Wire-Break Detection Yes–detects open circuits on passive/dry-contact wiring

Short-Circuit Protection Yes–per channel,auto-recovery

Galvanic Isolation Field-to-system:500 VAC RMS;Group isolation(per 8 channels)

Diagnostic Coverage>99%(per IEC 61508 FMEDA)

Hot-Swap Support Yes–in redundant HIMax racks with proper baseplate

LED Indicators

•Green RUN:Module operational

•Yellow DIAG:Diagnostic active(e.g.,wire break)

•Red ERR:Internal fault or communication loss

Power Consumption~3.8 W(from backplane)

Operating Temperature 0°C to+60°C

Dimensions Standard HIMax module:~240 mm(H)×35 mm(W)×180 mm(D)

Weight~0.85 kg

Certifications

•SIL 3 per IEC 61508:2010

•IEC 61511

•ATEX(II 3G Ex nA IIC T4 Gc)

•IECEx

•UL 61010-1,CE,RoHS

Mounting Slide-in module for HIMax carrier—secured with front screw

Technical Principles and Innovative Values

Innovation Point 1:High Channel Density with Safety Integrity–32 channels in a single slot reduce cabinet space and cost while maintaining SIL 3 compliance.

Innovation Point 2:Advanced Diagnostics–Wire-break detection ensures dangerous undetected faults are minimized,boosting safe failure fraction(SFF).

Innovation Point 3:Flexible Wiring Topology–Supports both active(sourced)and passive(dry contact)sensors—ideal for mixed legacy/new installations.

Innovation Point 4:Seamless Integration with HIMA Engineering Studio(ES)–Channel configuration,filtering,and diagnostics managed centrally.

Application Cases and Industry Value

In a German chemical plant,F7126 modules interface with over 500 emergency stop buttons and door interlocks on reactor skids.The consistent 24VDC input behavior and fast response(<10 ms)ensure machine safety systems meet ISO 13849 PL e requirements.

Similarly,a U.S.LNG export terminal uses F7126 in its flare ignition monitoring system.Despite high EMI from nearby compressors,the galvanic isolation prevents false signals—ensuring reliable flame-on confirmation.

Related Product Combination Solutions

HIMax Controllers:H41q,H51q,H61q–main safety CPUs

Digital Output Modules:e.g.,F7136(32-channel DO)–for solenoid/relay control

Analog I/O Modules:e.g.,F7216(AI),F7226(AO)–for pressure/temperature SIFs

HIMA Engineering Studio(ES):Configuration,logic programming,and diagnostics

HIMA SafeLink:For secure remote access and asset monitoring

Redundant Power Supplies:e.g.,F7011/F7012–ensure continuous I/O operation

Terminal Blocks:e.g.,F79xx series–removable for pre-wiring

Safety Networks:PROFIsafe,Modbus/TCP(via communication modules)

Installation,Maintenance,and Full-Cycle Support

Installation of the HIMA F7126:

Insert into designated I/O slot in HIMax rack

Secure with front-panel captive screw

Connect field wiring to compatible terminal block(e.g.,F7926)

Configure input type and filtering in HIMA Engineering Studio

Download configuration—module auto-initializes

Maintenance advantages:

Per-channel diagnostics visible in HIMA ES

Hot-swap in redundant systems eliminates downtime

LED status allows quick visual troubleshooting

We supply HIMA F7126 modules that are:

Factory-new(direct from HIMA)or professionally refurbished/tested

Fully validated on live HIMax test benches with simulated field signals

Verified for hardware revision and firmware compatibility

Packaged with ESD-safe materials and accompanied by test&certification reports

With deep expertise in functional safety systems and global access to HIMA components,we ensure your Safety Instrumented System(SIS)remains certified,compliant,and always ready to protect people,assets,and the environment.

Contact us for a customized solution—whether you’re commissioning a new SIS,replacing aging I/O,or building a strategic spare inventory for your HIMax infrastructure.

选择深圳长欣,选择放心,售后无忧 大量现货,当天顺丰发货!!!

HIMA F7126 Galvanically Isolated Input Module – Supports Fail-Safe Wiring in Oil, Gas & Chemical Plants插图1

qrf

HIMA F7126 Galvanically Isolated Input Module – Supports Fail-Safe Wiring in Oil, Gas & Chemical Plants插图2

qrf

Back to Top

Search For Products

Product has been added to your cart