HONEYWELL RM7895 A 1014
HONEYWELL RM7895 A 1014 is a microprocessor-based burner control module for commercial and industrial applications.It supervises the sequencing,ignition,flame sensing,and safe shutdown of gas,oil,or combination fuel burners.This module is part of the Honeywell 7800 series,a family of reliable burner controls designed for a wide range of combustion systems.
Technical Specifications
Parameter Value/Description
Model HONEYWELL RM7895 A 1014
Manufacturer Honeywell
Product Type Burner Control Module
Part Number RM7895A1014
Application Intermittent Pilot,On/Off,and Modulating Burners
Flame Safeguard 7800 Series
Flame Signal Rectification,UV,or IR Sensing(requires specific flame amplifier)
Voltage 120 VAC,50/60 Hz
Mounting Q7800A Universal Wiring Subbase
Safety Features Lockout,purge timing,trial for ignition
Key Features and Functionality
The RM7895 A 1014 module is the brain of a burner management system,offering critical features that ensure a burner operates safely and efficiently.Its microprocessor constantly monitors the burner’s sequence,from the initial pre-purge to post-purge shutdown.
Integrated Safety Timings:The module has built-in,non-adjustable timings for critical phases such as pre-purge(clearing unburned fuel),trial for ignition(the period for establishing a stable flame),and inter-purge(the time between burner cycles).These fixed timings simplify setup and guarantee a consistent safety protocol.
Flame Supervision:The RM7895 A 1014 works with various Honeywell flame amplifiers and detectors,including flame rectification rods,ultraviolet(UV)sensors,and infrared(IR)sensors.It continuously monitors the flame signal.If the flame is lost during operation,the module will initiate a safe shutdown and lockout,preventing unburned fuel from accumulating.
Diagnostics:The module provides diagnostic LEDs that offer visual feedback on the burner’s operational status.This simplifies troubleshooting for technicians,who can quickly identify the cause of a fault—like a failed ignition or loss of flame signal—without needing complex diagnostic tools.
Application Versatility:The RM7895 A 1014 is designed for on/off and modulating burners with an intermittent pilot.This makes it a versatile solution for a range of commercial and light industrial applications,including boilers,air heaters,and process ovens.
Common Applications
The HONEYWELL RM7895 A 1014 module is widely used in commercial and industrial settings where burner safety is critical.
Commercial and Industrial Boilers:It’s commonly found in steam and hot water boilers for process heating or building climate control.The module ensures the boiler’s burner ignites and operates safely,protecting both equipment and personnel.
Process Air Heaters:In manufacturing and food processing,air heaters are used for drying,curing,or baking.The module’s precise sequencing and flame supervision are essential for maintaining stable temperatures and preventing explosions.
Incinerators:For waste management or emissions control,the RM7895 A 1014 is used to control the burner in incinerators,ensuring a reliable and safe combustion process.
Related Products
The HONEYWELL RM7895 A 1014 module operates as part of a complete burner management system.Here are some related components:
Q7800A Universal Wiring Subbase:This is the required base for mounting the RM7895 A 1014 module.
R7847,R7848,R7849 Series Flame Amplifiers:These modules plug into the RM7895 and interpret the signal from the flame detector.
C7027 or C7035 Ultraviolet Flame Detectors:These sensors are used to”see”the flame and send a signal back to the control module via a flame amplifier.
S7800 Series Display Module:This optional module provides a digital readout and advanced diagnostics for the burner control system.
Installation and Maintenance
Installation of the RM7895 A 1014 module is straightforward.It snaps securely into the Q7800A subbase,which should be properly wired according to the manufacturer’s specifications.Always de-energize the system before installation to prevent electrical shock.Once installed,the module automatically performs self-diagnostics to verify its integrity.
For maintenance,the module is designed for reliability and requires little routine care.The key is to monitor its operational status through the on-board LEDs.If a lockout occurs,these lights will quickly guide a technician to the cause.The modular design of the 7800 series means the RM7895 A 1014 can be easily replaced if needed,minimizing downtime.Regular inspection of the flame sensor and wiring is also recommended to ensure the system’s continued safe operation.